1.This instrument is only suitable for single-phase 230V / 50Hz (with power supply voltage range
2.Wiring check: whether three LED indicators are correct, if two green indicators P-E and P-N are on, and red indicator is not on, then it is correct: the test can only be triggered if the wiring is correct.
3.Phase angle selection: you can choose to start the test from positive (0 °) or from half cycle negative (180 °);
4.“OL" is displayed for over range: when the test trip action time exceeds the maximum test time, the LCD will display "OL mS"
5.Automatic data holding: After test is completed, the displayed measurement results are held for a certain period of time;
6.AUTO RAMP test: The AUTO RAMP test can test tripping current and time simultaneously.
7.Shutdown alarm function: After 3 minutes of operation, the instrument will let out a shutdown beep alarm;
8.Built-in FUSE security protection;
23 + 5 ℃;Humidity:45%~75% RH; altitude≤2000m:)
Functions
|
Operation voltage (AC) |
Rated operating current(L△n) |
Fault action time(MAX) |
Accuracy |
|
Action current | Action time | ||||
X1/2 |
230V(Error range:-15%~+10%)
Frequency:50Hz |
10/20/30/100/300/500mA |
1000ms |
Error range:-10%~+10% |
+0.6% rdg +8dgt |
X1 |
10/20/30/100/300mA |
1000ms |
Error range:-10%~+10% |
||
500mA |
300ms |
||||
X5 |
10/20/30mA |
1000ms |
|||
AUTO RAMP test |
10/20/30/100/300/500mA |
(RAMPIncreasing step10%) L△n20%~110% |
Error range:-10%~+10% |